Energy storage & smart Grid PMG Converter Shore power supply Industrial power supply Power test equipment PV inverter Charging pile Aviation Power supply

Bi-directional inverter

The smart micro grid structure demands different for different load, but the basic unit containing distributed power (energy), energy storage device, and load management system. Most interface of the micro energy to the grid requirements is designed based on power electronic technology, to ensure the micro grid to run flexibility and reliability as a single system. Micro grid system with interconnection and independent (isolated) two stable operation condition and two corresponding transition state: on grid state and micro grid solution. 
According to micro grid structure and load condition, the smart micro grid system can be roughly divided into three different levels, the countryside and small islands smart micro grid system, town and medium-sized island smart micro grid system, counties and cities and large islands smart micro grid system. The three kinds of systems have their respective characteristics and  different complexity, also have different applications, and on the basis of the three kinds of systems also stretch out a variety of other types of different functional micro grid system.And design of intelligent network system, the most important is to adjust measures to local conditions

Bi-directional inverter

1、Bi-directional invert, maintain the balance of power system, to ensure the quality of load power supply

2、It can be long term running in110% rated output power .

3、On/off grid running function: The PCS can work in on /off grid state, and the two states can be switched automatically.

4、With the parallel function, easy to expension.

5、Suit for many kinds of battery, with the  floating, constant current, constant voltage, constant power and so on many kinds of charging and discharging mode.

6、The range of the DC input voltage is wide and the efficiency is high(96%)

7、With the R, L, C load 100% unbalanced three phase, it can supply the power for the  nonlinear impact and motor load

8、With many kinds of communication port, including the internet, RS 485, CAN and so on.

9、High efficiency: can be 97.2% with the transformer.

10、Accept the scheduling: Can be scheduled by the grid.

11、With kinds of charging and discharging methord

12、Expansibility

13、With the active power and reactive power adjustable function

Type

BNX-5KD

BNX-5KS

BNX-10KS

BNX-20KS

BNX-50KS

BNX-100KS

BNX-250KS

BNX-300KS

AC side parameter

Rated capacity

5KW

5KW

10kW

20kW

50 kW

100 kW

250kW

300KW

Overload

5.5KW

5.5KW

11kW

22 kW

55 kW

110 kW

275kW

330KW

On-grid charging mode

Rated grid voltage

220Vac/380 Vac

Grid voltage range

310~450Vac

Grid frequency

50Hz/60Hz

Total harmonic distortion(THD)

<3%

Power factor

≥0.99

Separated on-grid mode

Rated output voltage

380 Vac

Output voltage accuracy

<3%

Output frequency

50Hz/60Hz

Output over-voltage

>450 Vac

Output under-voltage

<310 Vac

DC voltage range

Max DC power

5.5kW

5.5kW

11kW

22 kW

55 kW

110 kW

275kW

330KW

DC voltage range

48-400Vdc

196-400Vdc

480Vdc-900Vdc

DC current ripple

<5%

System

Max efficiency

96.6%

Temperature

-25~+60°C

Humidity

0~95%,non condensing

Noise

<50dB

Protection

Polarity inverse,short circuit,island efficiency.overheat,overload.ground fault protection

Cooling method

Forced cooling

Protect degree

IP20

Indication

Touching screen

Communication

RS485(MODBUS protocol)

W×D×H(mm)

580*510*1350

540*500*860

580*515*1250

650*610*1560

800*600*2060

1000*800*2060

2000*800*2060

2000*800*2060

Weight (kg)

180

100

150

300

700

900

1300